humiSteam electrode steam humidifiers Installation Operation User Manual Read and save these instructions. Models UE001 to UE065 Single Cy
CAREL humiSteam 10 Water supply and drain connections are made according to the following diagram. Note: Drain line must be installed and plumbed
Installation, Operating & Maintenance Manual 11 1.4 Steam distribution 1.4.1A Duct injection NOTE: If the ventilated steam distributor is to be
CAREL humiSteam 12 Distributor pipes should be mounted per the diagrams shown below, with a minimum of 6” from the center of the distributor pipe t
Installation, Operating & Maintenance Manual 13 1.4.1B Room distribution blower units Refer to the manual supplied with the Room Distribution U
CAREL humiSteam 14 1.4.2 Steam Hoses NINETY PERCENT (90%) OF ALL OPERATION PROBLEMS ARE CREATED BY IMPROPER STEAM PIPING FROM THE HUMIDIFIER UNIT T
Installation, Operating & Maintenance Manual 15 1.5 Power wiring Check that the power supply voltage to be connected matches the value indicat
CAREL humiSteam 16 Model Voltage Code Voltage Phase NominalCurrent(Amps)Power(kW) Output(kg/hr)Output(lbs/hr)Turns Through TAM TA Rate U 208 - 1~N
Installation, Operating & Maintenance Manual 17 1.6 Connect Control Wiring A typical humidifier control system includes a wall or return duct
CAREL humiSteam 18 Remote Supervisor / Serial Communications: This is a standard RS485 serial connection. It is recommended to keep wiring under
Installation, Operating & Maintenance Manual 19 For Modulating Operation with External Controller: Connect any external controller (0-1 Vdc, 0
CAREL humiSteam 2
CAREL humiSteam 20 ASWH / ASDH – ASDH / ASDC Wall – Duct Temperature/Humidity Sensors Model Description Humidity (0-1 VDC or 4-20 mADC) ASWH100000
Installation, Operating & Maintenance Manual 21 HC-101 and HC-201 Wall and Duct Humidistats Mounting the HC-101 room humidistat: Mount the HC-
CAREL humiSteam 22 PC-301 Air Proving Switch Mounting the PC-301 air flow switch: Mount the airflow switch in the supply or return duct using the s
Installation, Operating & Maintenance Manual 23 2 Start-Up IMPORTANT WARNINGS: 1. Before starting, check that the humidifier is in perfect co
CAREL humiSteam 24 2.2 The HumiControl Controller 1: PRG - Access to most frequently used parameters. Also resets alarm relay. 2: SEL - Displays
Installation, Operating & Maintenance Manual 25 3 Operation 3.1 Display Information Pressing the SEL button displays the unit of measure curren
CAREL humiSteam 26 Code Range Default Unit Description P7 (1) St to 100 100 %RH Hi-limit set point P8 2.0 to 19.9 5 %RH Hi-limit differ
Installation, Operating & Maintenance Manual 27 0=0-1V; 1=0-10V; 2=2-10V; 3=0-20mA; A6 0 to 4 0 Type of outlet sensor; accessible only i
CAREL humiSteam 28 Parameters for setting the serial connections and remote control: Code Range Unit Description C0 1 to 6 1 Value normally d
Installation, Operating & Maintenance Manual 29 STANDARD CONFIGURATION SETTINGS HumiSteam Parameters H Controller Parameter DDC 0-10 vdc DDC
Installation, Operating & Maintenance Manual 3 IMPORTANT BEFORE INSTALLING OR HANDLING THE HUMIDIFIER PLEASE CAREFULLY READ AND FOLLOW THE I
CAREL humiSteam 30 3.6 Seasonal Shut Down During seasonal shut-down or alternatively shut-down for maintenance of the electrical parts and/or the pl
Installation, Operating & Maintenance Manual 31 3.8 Resetting the Hour Counter To reset the hour counter (parameter d4), proceed as follows: •
CAREL humiSteam 32 Controller ActionH Humivisor Causes Solution H Reset display Alarm relayReset relay EF E114 Lack of water 1. Check that the
Installation, Operating & Maintenance Manual 33 Controller Action H Humivisor Causes Solution H Reset display Alarm relay Reset relay E0 E1
CAREL humiSteam 34 Controller ActionH Humivisor Causes Solution H Reset display Alarm relay Reset relay Dr - Complete draining of the cylinder a
Installation, Operating & Maintenance Manual 35 3.10 Trouble-Shooting problem causes solutions the humidifier does not turn on 1. no electri
CAREL humiSteam 36 problem causes solutions Water in the cylinder turns black 1. minerals in the cylinder have overconcentrated and are deteriorat
Installation, Operating & Maintenance Manual 37 4 Maintenance 4.1 Periodic checks • After one hour of operation: For both disposable and clean
CAREL humiSteam 38 Wiring of cylinders for UE025, UE035, UE045, UE065 units and voltages Connection of single or three phase UE 001 to 015 models
Installation, Operating & Maintenance Manual 39 UE001-UE015 4.2.2 Maintenance of the other plumbing components IMPORTANT WARNINGS: • When clea
CAREL humiSteam 4 Table of Contents How The Humisteam Works...
CAREL humiSteam 40 4.3 Replacement Parts 4.3.1 Single Phase Humidifiers Standard spare parts Model UE001 UE003 UE005 UE009 Water parts fil
Installation, Operating & Maintenance Manual 41 Standard Spare Parts Model UE003 UE005 UE008 UE010 UE015 UE025 UE035 UE
CAREL humiSteam 42 electrode kit 460/3 VAC Low conductivity KITBLCT2C0 KITBLCT2C0 KITBLCT3C0 KITBLCT3C0 KITBLCT4D0 KITBLCT4C0 KITBLCT4C0 KITBL
Installation, Operating & Maintenance Manual 43 5 Wiring Diagrams UE001, UE003, UE005, UE009 Single Phase
CAREL humiSteam 44 UE003, UE005, UE008, UE010, UE015 Three Phase
Installation, Operating & Maintenance Manual 45 UE025, UE035, UE045, UE065 Three Phase
CAREL humiSteam 46 6 Technical Specifications UNIT MODEL NUMBER: Capacity, Amperage, Kilowatts VAC/ Phase Factor UE 001 UE 003 UE 005 UE 008 UE 009
Installation, Operating & Maintenance Manual 47 6.1 Model Numbers UE 025 H D 000 U 1 0 UE = Electrode Capacity H Control Power supply Version
CAREL humiSteam 48 CAREL USA, LLC 385 S. Oak Street Manheim, PA 17545 Form: +030221907, Rev. 0
Installation, Operating & Maintenance Manual 5 How The Humisteam Works HumiSteam is an electrode humidifier. It produces steam for humidificat
CAREL humiSteam 6 1 Installation 1.1 Positioning The HumiSteam has been designed for wall mounting (although it can be placed on a stand) and, since
Installation, Operating & Maintenance Manual 7 1.2 Mounting 1.2.1 Removing the front cover The front cover is secured by a capture screw locate
CAREL humiSteam 8 1.3 Plumbing 1.3.1 Water supply The HumiSteam must be supplied with water (not softened) having the following characteristics:
Installation, Operating & Maintenance Manual 9 See the following diagram for a drain line installation diagram Note: If utilizing the optional