EASY FREEZE (PZD*C0****): electronic controllers for low temperature ventilated refrigeration units
+050004122 - rel. 1.2 - 28.07.2011
Description
PJEZ* represent a range of electronic microprocessor controllers with LED display developed for the manage-
ment of refrigerating units, display cabinets and showcases.
Technical specifi cations
• Electronic controllers for low temperature ventilated refrigeration units
• Power supply 115 or 230Vac
• Ambient probe NTC
• Compressor relay 16A
• Defrost relay 8A
• Evaporator fan relay 8A
Display and functions
During normal operation, the controller displays the temperature read by probe 1. In addition, the display has
LEDs that indicate the activation of the control functions (see Table 1), while the 3 buttons can be used to
activate/deactivate some of the functions (see Table 2).
LEDs and associated functions
icon function normal operation start up
ON OFF blink
compressor
on off request ON
fan on off request ON
defrost on off request ON
alarm all no alarm - ON
Tab. 1
Table of functions activated by the buttons
button
normal operation
start up
pressing the button alone pressed together
up
ON/OFF
more than 3 s:
toggle ON/OFF
Pressed together start/stop
continuous cycle
-
down
defrost
more than 3 s:
start/stop defrost
for 1 s display
rmware vers. code
set mute - 1 s.: display/set the setpoint
- more than 3 s: access parameter
setting menu (enter password ‘22’)
- mute audible alarm (buzzer)
- for 1 s RESET
current
EZY set
Tab. 2
Setting the setpoint (desired temperature)
Step Action Effect Meaning
1
Keep SET button pressed for 2 s
After 1 sec currently setpoint value will
ash on display
It’s regulation setpoint
currently active
2 Press UP or DOWN buttons Setpoint value will chang Set desired value
3 Press SET button Controller will visualize temperature
read by probes again
Setpoint is modifi ed and
saved
Tab. 3
Accessing and setting the parameters
Step Action Effect Meaning
1 Keep SET button pressed
for 3 s
After 3 sec display will visualize “PS Password is requested
2 Press SET button again Display will visualize “0” blinking
3 Press UP or DOWN button Visualized value on display will change Insert password “22
4 Press SET button After 5 sec the fi rst parameter, “/5”, will be
visualized on display
It’s the name of the fi rst
parameter
5 Press UP or DOWN button Parameter list will be scrolled on display
(refer to Table of parameters)
Select desired parameter
6 Press SET button Display will visualize value of the selected
parameter
It’s the currently parameter
value
7 Press UP or DOWN button Parameter value visualized on display will
change
Set desired value
8 Press SET button Display will visualize parameter name
again
Attention: parameters
updating is not yet active
9 Repeat steps 5, 6, 7 and 8
for all desired parameters
10 Keep SET button
pressed for 5 s
Controller will visualize temperature read
by probes again
Attention: now parame-
ters updating will be active
Tab. 4
Dimensions (mm)
71x29
10
3
33
74
81
36
58
65,29
28.5
Fig.1
Panel mounting
Front (with 2 screws ø 2,5x12 mm)
max 2,5
1
2
3
Pozidriv type
Do not tighten
excessively
Fig.2
Rear (with 2 quick-fi t side brackets)
1
2
PUSH
serial conv. IROPZ485S0
prog. key IROPZKEY* or
PSOPZKEY*
Fig. 3
Electrical connections
230 Vac
Fig. 4
Use copper conductors only
Ref. C614A216/R0
12345 6 7
9 10 118
L
L N
115V~
8(4)A 10(10)A EN60730-1
8A 2FLA 12LRA 12A 10FLA 60LRA UL 873
DEF. T.
DI / NTC
AMB. T.
NTC
PROBES
SERIAL
CONV
PROG.
KEY
-10T50
250 Vac
12345 6 7
9 10 118
L
L N
Use copper conductors only
Ref. C614A217/R0
8(4)A 10(10)A EN60730-1
8A 2FLA 12LRA 12A 10FLA 60LRA UL 873
DEF. T.
DI / NTC
AMB. T.
NTC
PROBES
SERIAL
CONV
PROG.
KEY
-10T50
250 Vac
230V~
Fig. 5
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
PZD4C0H101
PZD4C0H001
PZD0C0P001