humiSteam electrode steam humidifiers Installation Operation User Manual Read and save these instructions. Models UE001 to UE065 Single Cy
CAREL humiSteam 10 Water supply and drain connections are made according to the following diagram. Note: Drain line must be installed and plumbe
Installation, Operating & Maintenance Manual 11 1.4 Steam distribution 1.4.1A Duct injection NOTE: If the ventilated steam distributor is to
CAREL humiSteam 12 Distributor pipes should be mounted per the diagrams shown below, with a minimum of 6” from the center of the distributor pipe
Installation, Operating & Maintenance Manual 13 1.4.1B Room distribution blower units Refer to the manual supplied with the Room Distribution
CAREL humiSteam 14 1.4.2 Steam Hoses NINETY PERCENT (90%) OF ALL OPERATION PROBLEMS ARE CREATED BY IMPROPER STEAM PIPING FROM THE HUMIDIFIER UNIT
Installation, Operating & Maintenance Manual 15 1.5 Power wiring Check that the power supply voltage to be connected matches the value indic
CAREL humiSteam 16 Model Voltage Code Voltage Phase Nominal Current (Amps) Power (kW) Output (kg/hr) Output (lbs/hr) Turns Through TAM TA Rate U
Installation, Operating & Maintenance Manual 17 1.6 Connect Control Wiring A typical humidifier control system includes a wall or return duc
CAREL humiSteam 18 Remote Supervisor / Serial Communications: This is a standard RS485 serial connection. It is recommended to keep wiring unde
Installation, Operating & Maintenance Manual 19 For Modulating Operation w ith External Controller: Connect any external controller (0-1 Vdc
CAREL humiSteam 2
CAREL humiSteam 20 ASWH / ASDH – ASDH / ASDC Wall – Duct Temperature/Humidity Sensors Model Description Humidity (0-1 VDC or 4-20 mADC) ASWH10000
Installation, Operating & Maintenance Manual 21 HC-101 and HC-201 Wall and Duct Humidistats Mounting the HC-101 room humidistat: Mount the H
CAREL humiSteam 22 PC-301 Air Proving Switch Mounting the PC-301 air flow switch: Mount the airflow switch in the supply or return duct using th
Installation, Operating & Maintenance Manual 23 2 Start-Up IMPORTANT WARNINGS: 1. Before starting, check that the humidifier is in perfect
CAREL humiSteam 24 2.2 The HumiControl Controller 1: PRG - Access to most frequently used parameters. Also resets alarm relay. 2: SEL - Display
Installation, Operating & Maintenance Manual 25 3 Operation 3.1 Display Information Pressing the SEL button displays the unit of measure curr
CAREL humiSteam 26 Code Range DefaultUnit Description P7 (1) St to 100 100 %RH Hi-limit set point P8 2.0 to 19.9 5 %RH Hi-limit differen
Installation, Operating & Maintenance Manual 27 0=0-1V; 1=0-10V; 2=2-10V; 3=0-20mA; A6 0 to 4 0 Type of outlet sensor; accessible only
CAREL humiSteam 28 Parameters for setting the serial connections and remote control: Code Range Unit Description C0 1 to 6 1 Value normally
Installation, Operating & Maintenance Manual 29 STANDARD CONFIGURATION SETTINGS HumiSteam Parameters H Controller Parameter DDC 0-10 vdc DD
Installation, Operating & Maintenance Manual 3 IMPORTANT BEFORE INSTALLING OR HANDLING THE HUMIDIFIER PLEASE CAREFULLY READ AND FOLLOW TH
CAREL humiSteam 30 3.6 Seasonal Shut Down During seasonal shut-down or alternatively shut-down for maintenance of the electrical parts and/or the
Installation, Operating & Maintenance Manual 31 3.8 Resetting the Hour Counter To reset the hour counter (parameter d4), proceed as follows:
CAREL humiSteam 32 Controller ActionH Humivisor Causes Solution H Reset display Alarm relay Reset relay EF E114 Lack of water 1. Check that
Installation, Operating & Maintenance Manual 33 Controller Action H Humivisor Causes Solution H Reset display Alarm relay Reset relay E0
CAREL humiSteam 34 Controller Action H Humivisor Causes Solution H Reset display Alarm relay Reset relay Dr - Complete draining of the cylinde
Installation, Operating & Maintenance Manual 35 3.10 Trouble-Shooting problem causes solutions the humidifier does not turn on 1. no elect
CAREL humiSteam 36 problem causes solutions Water in the cylinder turns black 1. minerals in the cylinder have overconcentrated and are deteri
Installation, Operating & Maintenance Manual 37 4 Maintenance 4.1 Periodic checks • After one hour of operation: For both disposable and cle
CAREL humiSteam 38 Wiring of cylinders for UE025, UE035, UE045, UE065 units and v oltages Connection of single or three phase UE 001 to 015 mode
Installation, Operating & Maintenance Manual 39 UE001-UE015 4.2.2 Maintenance of the other plumbing components IMPORTANT WARNINGS: • When c
CAREL humiSteam 4 Table of Contents How The Humisteam Works...
CAREL humiSteam 40 4.3 Replacement Parts 4.3.1 Single Phase Humidifiers Standard spare parts Model UE001 UE003 UE005 UE009 Water parts f
Installation, Operating & Maintenance Manual 41 Standard Spare Parts ModelUE003 UE005 UE008 UE010 UE015 UE025 UE03
CAREL humiSteam 42 electrode kit 460/3 VAC Low conductivity KITBLCT2C0 KITBLCT2C0 KITBLCT3C0 KITBLCT3C0 KITBLCT4D0 KITBLCT4C0 KITBLCT4C0
Installation, Operating & Maintenance Manual 43 5 Wiring Diagrams UE001, UE003, UE005, UE009 Single Phase
CAREL humiSteam 44 UE003, UE005, UE008, UE010, UE015 Three Phase
Installation, Operating & Maintenance Manual 45 UE025, UE035, UE045, UE065 Three Phase
CAREL humiSteam 46 6 Technical Specifications UNIT MODEL NUMBER: Capacit y, Amperage, Kilowa tts VAC/ Phase Factor UE 001 UE 003 UE 005 UE 008 UE
Installation, Operating & Maintenance Manual 47 6.1 Model Numbers UE 025 H D 000 U 1 0 UE = Electrode Capacity H Control Power supply
CAREL humiSteam 48 CAREL USA, LLC 385 S. Oak Street Manheim, PA 17545 Form: +030221907, Rev
Installation, Operating & Maintenance Manual 5 How The Humisteam Works HumiSteam is an electrode humidifier. It produces steam for humidifi
CAREL humiSteam 6 1 Installation 1.1 Positioning The HumiSteam has been designed for wall mounting (although it can be placed on a stand) and, sin
Installation, Operating & Maintenance Manual 7 1.2 Mounting 1.2.1 Removing the front cover The front cover is secured by a capture screw loca
CAREL humiSteam 8 1.3 Plumbing 1.3.1 Water supply The HumiSteam must be supplied with water (not softened) having the following characteristics:
Installation, Operating & Maintenance Manual 9 See the following diagram for a drain line installation diagram Note: If utilizing the option