EASY COOL (PZD*S*P***): electronic controllers for normal temperature static refrigeration units
+050004121 - rel. 1.1 - 28.07.2011
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
Description
PJEZ* represents a range of electronic microprocessor controllers with LED display developed for the manage-
ment of refrigerating units, display cabinets and showcases; are designed for the management of static refrigera-
ting units (no fan on the evaporator) operating at temperatures above 0°C.
Technical specifi cations
• Electronic controllers for normal temperature static refrigeration units
• Power supply 115Vac or 230Vac
• Ambient probe NTC
• Compressor relay 16A
Display and functions
During normal operation, the controller displays the value of the temperature read by probe. In addition, the
display has LED that indicate the activation of the control functions (see Tab. 1), while the 3 buttons can be used
to activate/deactivate some of the functions (see Tab. 2).
Compressor LED signals
icon function normal operation start up
ON OFF blink
compressor status on off ON request in
progress
ON
Tab. 1
Table of functions activated by the buttons
button
normal operation
start up
pressing the button alone pressed together
up
ON/OFF
more than 3 s:
toggle ON/OFF
Pressed together start/
stop
continuous cycle
-
down
defrost
more than 3 s:
start/stop defrost
for 1 s display fi rmware
vers. code
set mute - 1 s.: display/set the set point
- more than 3 s: access
parameter setting menu
(enter password ‘22’)
- for 1 s RESET current
EY set
Tab. 2
Setting the setpoint (desired temperature)
Step Action Effect Meaning
1
Keep SET button pressed
for 2 s
After 1 sec currently setpoint value will
ash on display
It’s regulation setpoint
currently active
2 Press UP or DOWN
buttons
Setpoint value will chang Set desired value
3 Press SET button Controller will visualize temperature read
by probes again
setpoint is modifi ed and
saved
Tab. 3
Accessing and setting the parameters
Step Action Effect Meaning
1 Keep SET button
pressed for 3 s
After 3 s display will visualize “PS Password is requested
2 Press SET button again Display will visualize “0” blinking
3 Press UP or DOWN button Visualized value on display will change Insert password “22
4 Press SET button After 5 s the fi rst parameter, “/5”, will be
visualized on display
It’s the name of the fi rst
parameter
5 Press UP or DOWN button Parameter list will be scrolled on display
(refer to Table of parameters)
Select desired parameter
6 Press SET button Display will visualize value of the selec-
ted parameter
It’s the currently parameter
value
7 Press UP or DOWN button Parameter value visualized on display
will change
Set desired value
8 Press SET button Display will visualize parameter name
again
Attention: parameters
updating is not yet active
9 Repeat steps 5, 6, 7 and 8 for
all desired parameters
10 Keep SET button
pressed for 5 s
Controller will visualize temperature
read by probes again
Attention: now parameters
updating will be active
Tab. 4
Dimensions (mm)
38,29
31
28.5
10
3
71x29
36
81
74
33
PZD0SNP0E1
PZD4S0P001
PZD4S0P101
10
3
58
65,29
28.5
Panel mounting
max 2,5
1
2
3
Pozidriv type
Do not tighten
excessively
Front (with 2 screws ø 2,5x12 mm)
Rear (with 2 quick-fi t side brackets) If necessary, remove the covers to simplify wiring
1
2
PUSH
PZD0SNP0E1
Fig.4
1
2
PUSH
PZD4S0P001, PZD4S0P101
Fig. 3
Electrical connections
230 Vac
345 67
9 10 118
L
L N
115V~
Use copper conductors only
Ref. C614A215/R0
EN60730-1 12(2)A
UL 873 12A 5FLA 30LRA
AMB. T.
NTC
PROBES
SERIAL
CONV
PROG.
KEY
-10T50
DI / NTC
250 Vac
3 4 5 6 7
9 10 118
L
L N
230V~
Use copper conductors only
Ref. C614A198/R0
EN60730-1 12(2)A
UL 873 12A 5FLA 30LRA
AMB. T.
NTC
PROBES
SERIAL
CONV
PROG.
KEY
-10T50
250 Vac
Fig.1
Fig.2
Fig.5
PZD0SNP0E1
PZD4S0P101
PZD4S0P001
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - 3 4 5 6 7

EASY COOL (PZD*S*P***): electronic controllers for normal temperature static refrigeration units+050004121 - rel. 1.1 - 28.07.2011NO POWER & SIGNA

Seite 2 - CAREL INDUSTRIES HQs

+050004121 - rel. 1.1 - 28.07.2011 CAREL INDUSTRIES HQsVia dell’Industria, 11 - 35020 Brugine - Padova (Italy)Tel. (+39) 0499716611 – Fax (+39) 049

Kommentare zu diesen Handbüchern

Keine Kommentare